AS-Interface master | VAM-CTR-KF-R3

Article: VAM-CTR-KF-R3
Name: AS-Interface master | VAM-CTR-KF-R3
Manufacturer: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Îáîðóäîâàíèå ñíÿòî ñ ïðîèçâîäñòâà, äëÿ óòî÷íåíèÿ çàìåíû ñâÿæèòåñü ñ íàìè sales@quad-industry.com

  • Stand-alone master with PLC functionality
  • Two-digit LC display
  • Voltage supply from AS-Interface
  • Automatic baud rate detection
  • Programmable slave addresses
  • Display of detected slaves
  • Fault diagnosis
  • Parameterization and monitor software
  • Power Rail connection
  • RS 422 interface

Datasheet as PDF in following languages:


Technical Data: VAM-CTR-KF-R3

Product Description
AS-Interface master RS 422 cabinet module
General specifications
AS-Interface specificationV2.0
Diagnostics functionintegrated
Indicators/operating means
Display2-digit LC Display for address and error message
LED AS-i ACTIVEAS-Interface operation normal; LED green
LED CONFIG ERRconfiguration error; LED red
LED PRG ENABLEautom. programming; LED green
LED POWERvoltage ON; LED green
LED PRG MODEprojecting mode active; LED yellow
LED SER ACTIVEinterface in operation; LED green
LED U AS-iAS-Interface voltage; LED green
Switch SETSelection and setting of a slave address
Button MODEMode selection/save configuration
Electrical specifications
Insulation voltage≥ 500 V
Rated operating voltagefrom AS-Interface
Rated operating current≤ 150 mA
Interface
Interface type RS 422
Transfer rate1200 , 2400 , 4800 , 9600 , 19200 , 38400 or 57600 Bit/s , Automatic baud rate detection
Connection
AS-Interfaceremovable coded terminals, Power Rail
Compliance with standards and directives
Standard conformity
Protection degreeEN 60529
Ambient conditions
Ambient temperature0 ... 55 °C (32 ... 131 °F)
Storage temperature-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Protection degreeIP20
Mass420 g
Construction typeLow profile housing , plastic