AS-Interface repeater | VAR-KE2

Article: VAR-KE2
Name: AS-Interface repeater | VAR-KE2
Manufacturer: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Îáîðóäîâàíèå ñíÿòî ñ ïðîèçâîäñòâà, äëÿ óòî÷íåíèÿ çàìåíû ñâÿæèòåñü ñ íàìè sales@quad-industry.com

  • Line lengthening by 100 m (max. 2 repeater in series)
  • Galvanic isolation between AS-Interface circuits 1 and 2
  • No parameterization
  • Need no specific address on the AS-Interface bus
  • Housing with removable terminals

Datasheet as PDF in following languages:


Technical Data: VAR-KE2

Product Description
AS-Interface repeater
General specifications
UL File NumberE223772
Functional safety related parameters
MTTFd200 a at 30 °C
Indicators/operating means
LED FAULTerror display; LED red
red: communication error
LED PWRAS-Interface voltage; LED green
Electrical specifications
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current60 mA (per strand element), 120 mA (total)
Standard conformity
Electromagnetic compatibilityaccording EN 50295
Ambient conditions
Ambient temperature0 ... 55 °C (32 ... 131 °F)
Storage temperature-25 ... 75 °C (-13 ... 167 °F)
Mechanical specifications
Protection degreeIP20 according to EN 60529
Connectionremovable terminals, terminal connection ≤ 2.5 mm2
Material
HousingPA 66-FR
MountingDIN mounting rail


Back to the section