B7D-40-00-05 Mini Contactor | GJL1317201R0005 | B7D-40-00-05

Артикул: presentation.jpg, presentation.jpg, presentation.jpg
Наименование: B7D-40-00-05 Mini Contactor | GJL1317201R0005 | B7D-40-00-05
Производитель: ABB
Картинки описания: GJL1317201R0005


General Information
Extended Product Type:
B7D-40-00-05
Product ID:
GJL1317201R0005
EAN:
4013614262883
Catalog Description:
B7D-40-00-05 Mini Contactor
Long Description:
The B7D-40-00 mini contactor is a compact 4 pole contactor with screw terminals. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors are used in residential buldings, commercial buildings and industrial applications for the control of single or three-phase loads up to 5.5 kW (AC-3) and 20 A / 690 V (AC-1) or switching of control signals. The mini contactor has a build-in surge suppressor diode. Further features are the noiseless and hum-free coil, the integrated overvoltage protection, a switch position indication and the integrated possibility for rail or wall mounting.
 
Ordering
EAN:
4013614262883
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85365080
Dimensions
Product Net Width:
52.5 mm
Product Net Height:
57.5 mm
Product Net Depth:
46.5 mm
Product Net Weight:
0.175 kg
Container Information
Package Level 1 Units:
10 piece
Package Level 1 Width:
115.0 mm
Package Level 1 Height:
54.0 mm
Package Level 1 Length:
280.0 mm
Package Level 1 Gross Weight:
1.820 kg
Package Level 1 EAN:
4013614420153
Technical
Number of Poles:
4
Mini Contactor Type:
Mini Contactor
Rated Operational Voltage (Ue):
Main Circuit 12 ... 690 V AC
Rated Frequency (fr):
Control Circuit DC
Main Circuit DC
Main Circuit 50/60 Hz
Rated Impulse Withstand Voltage (Uimp):
Main Circuit 6 kV
Rated Insulation Voltage (Ui):
690 V
Number of Main Contacts NC:
0
Number of Main Contacts NO:
4
Rated Operational Current AC-1 (Ie):
(220/240V) 40??C 20 A
(380/440V) 40??C 20 A
(690V) 40??C 6 A
(220/240V) 55??C 16 A
(380/440V) 55??C 16 A
(690V) 55??C 6 A
Rated Operational Power AC-3 (Pe):
(220 / 230 / 240V) 3 kW
(400V) 5.5 kW
(440V) 5.5 kW
(500V) 5.5 kW
(690V) 3 kW
Rated Short-time Withstand Current (Icw):
at 40??C Ambient Temp, in Free Air, from a Cold State 10s 96 A
Number of Auxiliary Contacts NC:
0
Number of Auxiliary Contacts NO:
0
Rated Control Circuit Voltage (Uc):
220 ... 240 V DC
Coil Operating Limits:
(acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at ?? тЙд 55 ??C)
Degree of Protection:
IP20
Mechanical Durability:
10000000 cycle
Minimum switching capacity [V/mA]:
>17 V
>200 mA
Maximum Electrical Switching Frequency:
AC-1 300 cycles per hour
AC-3 600 cycles per hour
AC-15 600 cycles per hour
DC-13 600 cycles per hour
DC-3 600 cycles per hour
DC-1 600 cycles per hour
Connecting Capacity-Main Circuit:
Rigid 1/2x 1 ... 4 mm??
Flexible with Ferrule 1/2x 1 ... 2.5 mm??
Flexible with Insulated Ferrule 1/2x 1 ... 2.5 mm??
Flexible 1/2x 1 ... 2.5 mm??
Connecting Capacity-Control Circuit:
Rigid 1/2x 1 ... 4 mm??
Flexible with Ferrule 1/2x 1 ... 2.5 mm??
Flexible with Insulated Ferrule 1/2x 1 ... 2.5 mm??
Flexible 1/2x 1 ... 2.5 mm??
Wire Stripping Length:
Main Circuit 9 mm
Tightening Torques:
Main Circuit 0.8 ... 1.1 N??m
Control Circuit 0.8 ... 1.1 N??m
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Power Loss:
Per Pole 2 W
Standards:
IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1, UL508, CSA 22.2 No. 14
Environmental
Ambient Air Temperature:
Operation -25 тАж. +55 ??C
Storage -40 тАж+80 ??C
Maximum Operating Altitude Permissible:
2000 m
Resistance to Shock acc. to IEC 60068-2-27:
11 ms Pulse 15g
Resistance to Vibrations acc. to IEC 60068-2-6:
5g / 5 тАж 150 Hz
RoHS Status:
Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical UL/CSA
Maximum Operating Voltage UL/CSA:
Main Circuit 600 V AC
Connecting Capacity-Main Circuit UL/CSA:
Stranded 1/2x 22 ... 10 AWG
Horse Power Rating UL/CSA:
208V AC Three Phase 3 Hp
220 ... 240V AC Three Phase 5 Hp
440 ... 480V AC Three Phase 5 Hp
550 ... 600V AC Three Phase 5 Hp
Tightening Torques UL/CSA:
Main Circuit 7 in??lb
Control Circuit 7 in??lb
General Use Rating UL/CSA:
600V AC 16 A
Certificates and Declarations (Document Number)
BV Certificate:
CB Certificate:
CCC Certificate:
Declaration of Conformity - CE:
DNV Certificate:
GL Certificate:
GOST Certificate:
LR Certificate:
RMRS Certificate:
RoHS Information:
UL Certificate:
Classifications
Object Classification Code:
Q
ETIM 4.0:
EC000066 - Magnet contactor, AC-switching
ETIM 5.0:
EC000066 - Magnet contactor, AC-switching
UNSPSC:
39121529