4 poles | 1SDA066554R1

Артикул: 1SDA066554R1
Наименование: 4 poles | 1SDA066554R1
Производитель: ABB
Картинки описания: AP3106_FORMULA_A2_1P_1_L2_720.jpg, AP3106_FORMULA_A2_1_L2_720.jpg, AP3106_FORMULA_A2_2P_1_L2_720.jpg, AP3106_Group_FORMULA_3-4_1_L2_720.jpg


General Information
Product ID:
1SDA066554R1
EAN:
8015644693268
Catalog Description:
A2B 250 TMF 125-1250 4p F F
Long Description:
Automatic moulded case circuit-breakers, SACE FORMULA A2, Icu 415 V AC = 18kA, Size Iu = 250A , Thermomagnetic trip unit with fixed thermal and magnetic threshold, In = 125A, Im = 1250A, 4 poles, Version = Fixed, connection terminal = Front terminal
 
Ordering
EAN:
8015644693268
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85362090
Dimensions
Product Net Width:
140 mm
Product Net Height:
150 mm
Product Net Depth:
60 mm
Product Net Weight:
1.45 kg
Container Information
Package Level 1 Units:
1 piece
Package Level 1 Width:
162 mm
Package Level 1 Height:
120 mm
Package Level 1 Length:
155 mm
Package Level 1 Gross Weight:
1.8 kg
Package Level 1 EAN:
8015644693268
Additional Information
Electrical Durability:
120 cycles per hour
4000 cycle
Mechanical Durability:
Nr. Operations 240 cycles per hour
Nr. Operations 10000 cycle
Number of Poles:
4
Opening Time:
CB with SOR 15 ms
CB with UVR 15 ms
Power Loss:
Per Pole 7 W
Product Main Type:
SACE FORMULA
Product Name:
A2
Rated Current (In):
125 A
Rated Impulse Withstand Voltage (Uimp):
6 kV
Rated Insulation Voltage (Ui):
690 V
Rated Service Short-Circuit Breaking Capacity (Ics):
(240V) 12.5 kA
(380V AC) 9 kA
(415V AC) 9 kA
(440V AC) 7.5 kA
(480V AC) 7.5 kA
(500V AC) 2.5 kA
(250V DC) 2 poles in series 9 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(240V) 25 kA
(380V AC) 18 kA
(415V AC) 18 kA
(440V AC) 15 kA
(480V AC) 15 kA
(500V AC) 5 kA
(250V DC) 2 poles in series 18 kA
Version:
Fixed
Certificates and Declarations (Document Number)
Declaration of Conformity - CE:
Environmental Information:
Classifications
Object Classification Code:
Q