TRANSFORMER SITAS; PHASES:3; PN/PN(S6)(KVA):8 /29,6; UPRI(V):Y500-440-380+/-20/D289- 254-220+/-11; USEC(V):Y 400 / D 230; ISEC(A):11,5-20,00; F(HZ):50...60; VECTOR GR./SHIELD WNG.:IIIIII0 /0; TA/ISOKL:55 /H; IP00; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:SCREW; EN 61558-2-1, -2-2, -2-4 >UL/CSA-RECOGNIZED< >CONTROL CIRCUIT TRANSFORMER< >ISOLATION TRANSFORMER< |
|
General technical details: |
product designation | | transformer SITAS |
product brand name | | SIDAC |
Operating apparent output / rated value | V·A | 8,000 |
Efficiency | | 0.94 |
Manner of switching for transformers | | IIIiii0 |
Verification of suitability | | CE / cRUus |
Product function | | |
| | No |
| | No |
- short circuit and overload protection
| | No |
Number of the protective coils | | 0 |
Short-term vector power | V·A | 31,700 |
Relative short-circuit voltage | % | 3.99 |
|
Inputs: |
Phase number / of the inputs | | 3 |
Input voltage | | |
| V | 520 |
| V | 500 |
| V | 480 |
| V | 460 |
| V | 440 |
| V | 420 |
| V | 400 |
| V | 380 |
| V | 360 |
| V | 300 |
| V | 289 |
| V | 277 |
| V | 266 |
| V | 254 |
| V | 240 |
| V | 230 |
Electrical input frequency | | |
| Hz | 50 |
| Hz | 60 |
|
Outputs: |
Phase number / of the outputs | | 3 |
Output voltage | | |
| V | 400 |
| V | 230 |
Electrical output frequency | | |
| Hz | 60 |
| Hz | 50 |
|
Ambient conditions: |
Thermal class / according to IEC 60085 | | H |
Ambient temperature / rated value | °C | 55 |
Protection class IP | | IP00 |
|
Mechanical design: |
Design of the electrical connection | | |
- secondary side / for main current circuit
| | screw-type terminals |
- at the input / for main current circuit
| | screw-type terminals |
Type of mounting | | screws |
Construction form of the iron core | | 3UI 180/75 |
Width | m | 0.36 |
Height | m | 0.32 |
Depth | m | 0.268 |
|
Certificates/approvals: | | |
General Product Approval | Shipping Approval | other | Назад в раздел
|
|