| Similar to image | | SENTRON PAC3200; LCD; 96X96MM POWER MONITORING DEVICE PANEL MOUNT TYPE FOR MEASUREMENT OF ELECTR. VALUES VAUX: 110-340VDC / 95-240VAC VIN: MAX.690/400V; 45-65HZ AMPIN: X/1A OR X/5A AC COMPRESSION TYPE TERMINALS |
|
General technical data: |
product designation | | multimeter |
product brand name | | SENTRON |
Product-type designation | | PAC3200 |
Size of multimeter / company-specific | | size 96 |
Design of the product | | basic |
Product function | | |
| | Yes |
| | Yes |
| | Yes |
- reactive power measurement
| | Yes |
| | Yes |
| | Yes |
Item designation | | |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | P |
- according to DIN EN 61346-2
| | P |
|
Measurement: |
Measuring methode | | |
| | RMS |
| | TRMS |
Type of measured value detection | | complete |
Curve form of the voltage | | sinusoidal or distorted |
Measurable line frequency | Hz | 45… 65 |
Operating mode for measured value detection | | |
- automatic line frequency detection
| | Yes |
| | No |
| | No |
|
Measuring inputs for voltage: |
Measurable supply voltage | | |
- between (PE)N and L / for AC / maximum nominal value
| V | 400 |
- between the outer conductors / for AC / maximum nominal value
| V | 690 |
- between (PE)N and L / for AC
| V | 40… 480 |
- between the outer conductors / for AC
| V | 70… 831 |
Supply voltage / between the outer conductors / for AC | | |
| V | 831 |
Measuring category / for voltage measurement | | CATIII |
Outer conductors and neutral conductors internal resistance | | |
| M? | 1.05 |
Power consumption / for voltage measurement | | |
| mW | 220 |
Measuring range extension for voltages | | |
- with external voltage transformers
| | Yes |
|
Measuring inputs for current: |
Measurable current | | |
- 1 / for AC / nominal value
| A | 1 |
- 2 / for AC / nominal value
| A | 5 |
Relative measurable current / for AC | % | 1… 120 |
Continuous current / for AC / maximum permissible | A | 10 |
Short-time current resistance (Icw) / limited to 1 s / rated value | A | 100 |
Zero-point suppression / for current measurement | | 0.1 ... 10 % |
Measuring category / for current measurement | | CATIII |
Measuring range extension for currents | | |
- with external current transformers
| | Yes |
|
Fault limits: |
Reference condition / for metering precision | | according to IEC62053-22 and IEC62053-23 |
Formula for relative total measurement inaccuracy | | |
- for measured variable voltage
| | +/- 0.3 % |
- for measured variable current
| | +/- 0.2 % |
- for measured variable output
| | +/- 0.5 % |
- for measured variable output factor
| | +/- 0.5 % |
- for measured variable reactive energy
| | Class 2 according to IEC61557-12 and/or IEC62053-23 |
|
Supply voltage: |
Design of the power supply | | power supply with a wide range of voltages |
Type of voltage / of supply voltage | | AC/DC |
Relative symmetrical tolerance / of the supply voltage | % | 10 |
Measuring category / supply voltage | | CATIII |
Supply voltage / 1 / at AC | V | 95… 240 |
Apparent power consumption | | |
- without expansion module(s) / typical
| V·A | 6 |
- with expansion module(s) / maximum
| V·A | 8 |
Supply voltage / 1 / for DC | V | 140… 340 |
|
Digital input: |
Number of digital inputs | | 1 |
Input voltage / at the digital input | | |
| V | 24 |
- final value for signal<1>-recognition
| V | 8 |
- initial value for signal<1>-recognition
| V | 13 |
Input current / at the digital input | | |
| mA | 7 |
Initial delay time / at the digital input | | |
- for signal <1> after <0> / maximum
| ms | 5 |
- for signal <0> after <1> / maximum
| ms | 5 |
|
Digital output: |
Number of digital outputs | | 1 |
Design of digital outputs | | switching or pulse output function |
Norm / for impulse equipment | | according to IEC62053-31 |
Pulse duration | ms | 30… 500 |
Adjustable time period / minimum | ms | 10 |
Operating
|