| Similar to image | | SENTRON PAC3100; LCD; 96X96MM POWER MONITORING DEVICE PANEL MOUNT TYPE FOR MEASUREMENT OF ELECTR. VALUES UC: 110-250VDC / 100-240VAC UE: MAX.480/277V; 45-65HZ IE: X/5A AC TERMINAL CONNECTION |
|
General technical data: |
product designation | | multimeter |
product brand name | | SENTRON |
Product-type designation | | PAC3100 |
Size of multimeter / company-specific | | size 96 |
Design of the product | | basic |
Product function | | |
| | Yes |
| | Yes |
| | Yes |
- reactive power measurement
| | Yes |
| | No |
| | Yes |
Item designation | | |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | P |
- according to DIN EN 61346-2
| | P |
|
Measurement: |
Measuring methode | | |
| | TRMS |
| | TRMS |
Type of measured value detection | | complete |
Curve form of the voltage | | sinusoidal or distorted |
Measurable line frequency | Hz | 45… 65 |
Operating mode for measured value detection | | |
- automatic line frequency detection
| | Yes |
| | No |
| | No |
|
Measuring inputs for voltage: |
Measurable supply voltage | | |
- between (PE)N and L / for AC / maximum nominal value
| V | 277 |
- between the outer conductors / for AC / maximum nominal value
| V | 480 |
- between (PE)N and L / for AC
| V | 11.5… 332.4 |
- between the outer conductors / for AC
| V | 20… 576 |
Supply voltage / between the outer conductors / for AC | | |
| V | 576 |
Measuring category / for voltage measurement | | CATIII |
Outer conductors and neutral conductors internal resistance | | |
| M? | 0.84 |
Power consumption / for voltage measurement | | |
| mW | 131.2 |
Measuring range extension for voltages | | |
- with external voltage transformers
| | Yes |
|
Measuring inputs for current: |
Measurable current | | |
- 1 / for AC / nominal value
| A | 5 |
Relative measurable current / for AC | % | 0.2… 120 |
Continuous current / for AC / maximum permissible | A | 10 |
Apparent power consumption / for current measurement | | |
- with measuring range 5 A / per phase
| mVA | 500 |
Short-time current resistance (Icw) / limited to 1 s / rated value | A | 100 |
Zero-point suppression / for current measurement | | 10 mA |
- for neutral conductor current
| | 45 mA |
Measuring category / for current measurement | | CATIII |
Measuring range extension for currents | | |
- with external current transformers
| | Yes |
|
Fault limits: |
Reference condition / for metering precision | | according to IEC61557-12 (K55) |
Formula for relative total measurement inaccuracy | | |
- for measured variable voltage
| | +/- 1.0 % |
- for measured variable current
| | +/- 1.0 % |
- for measured variable output
| | +/- 1.0 % |
- for measured variable active power
| | +/- 1 % |
- for measured variable reactive power
| | +/- 3 % |
- for measured variable output factor
| | +/- 1 % |
- for measured variable active energy
| | Class 1 according to IEC 61557-12 and IEC62053-21 |
- for measured variable reactive energy
| | Class 3 according to IEC61557-12 and IEC62053-23 |
|
Supply voltage: |
Design of the power supply | | power supply with a wide range of voltages |
Type of voltage / of supply voltage | | AC/DC |
Relative symmetrical tolerance / of the supply voltage | % | 10 |
Measuring category / supply voltage | | CATIII |
Supply voltage / 1 / at AC | V | 100… 240 |
Supply voltage frequency | | |
| Hz | 50 |
| Hz | 60 |
Apparent power consumption | | |
- without expansion module(s) / typical
| V·A | 10 |
Supply voltage / 1 / for DC | V | 110… 250 |
|
Digital input: |
Number of digital inputs | | 2 |
Design of the switching input | | Self-supplied |
Operating conditions for digital inputs / external voltage supply | | No |
Input voltage / at the digital input | | |
| V | 30 |
Input current / at the digital input | | |
- final value for signal<0>-recognition
| mA | 0.5 |
- initial value for signal<1>-recognition
| mA | 2.5 |
Load impedance / at the digital input | | |
- initial value for signal<0> detection
| ? |
|