SmartVFD BYPASS, 230VAC, 50 HP,NEMA 12 Enclosure, Three Contactor Bypass || HVFDSB3B0500G230/U

Артикул: HVFDSB3B0500G230/U
Наименование: SmartVFD BYPASS, 230VAC, 50 HP,NEMA 12 Enclosure, Three Contactor Bypass
Производитель: Honeywell


Overview

The SmartVFD BYPASS is available in four configurations to meet your application needs: Disconnect Only, Two Contractor Bypass, Three Contractor Bypass, and Three Contractor with Auto-Bypass.

Features

  • Provides an economical means of bypassing the VFD
  • Freeze/Fire/Smoke Interlock
  • Fused Disconnect on some models
  • 3-Contactor bypass provides VFD isolation from power with motor running in BYPASS mode
  • 3-Contactor bypass provides TEST position powers the VFD without sending power to the motor
  • 3-Contactor Bypass with Auto-Bypass adds the control capabilities below to the standard three Contactor Bypass

Product Specifications

Dimensions (in.)
40.5 x 60 x 14
Dimensions (mm)
1028.7 x 1524 x 355.6
Weight (lb)
Contact Customer Care
Weight (kg)
Contact Customer Care
Frequency
0 Hz to 320 Hz
Voltage
230 Vac
Operating Temperature Range (F)
14 F to 122 F
Operating Temperature Range (C)
-10 C to 50 C
Enclosure
NEMA 12
Relay Outputs
Max. switching load: 250Vac/2A or 250Vdc/0,4A
Horsepower
50 HP
Current Ratings
140 A
Analog Current Output
0 (4) - 20 mA, max 500 ohm
Bypass
Drive with 3 contactor bypass
Auto Bypass
No
Drive Family
SmartVFD HVAC
Contactor
3 Contactors
Disconnect Type
Fused
Pilot Lights
Yes
Drive Input Disconnect
Yes
Drive Input Fuses
Yes
Type of RFI Filter
EMC Filter
Continuous Output Current
overload 1.5 x High overload current (1min/10min), overload 1.1 x Low overload current (1min/10min)
Starting Torque
Depends on the Motor
Acceleration time
0.1 - 3000 sec
Deceleration time
.1 - 3000 sec
Analog Voltage Input
0 - 10 Vdc , 200K ohm
Analog Current Input
0 (4) - 20 mA, 250 ohm differential
Digital Output
Open collector, max. load 48V/50mA
Reference Output Voltage
Maximum Load 10mA
Auxiliary Voltage
? 20%, max. load 50 mA
Frame Type
8

Marketing Collateral

Sales/Promotional Materials-Commercial Field Devices

Sales/Promotional Materials-SmartVFD HVAC Bypass (Spanish)

Sales/Promotional Materials-Variable Frequency Drives - SmartVFD Selection Guide (Spanish)

Sales/Promotional Materials-SmartVFD HVAC and Bypass

Sales/Promotional Materials-Variable Frequency Drives - SmartVFD Selection Guide

Sales/Promotional Materials-SmartVFD HVAC and Bypass for Electrical Channel

Owners Manual

Operator/Owner Materials-Smart COMPACT VFD

Operator/Owner Materials-Honeywell SmartVFD BACnet Protocol Installation and UserТs manual

Wiring-Fused Disconnect Wiring Diagram

Wiring-Contactor Wiring Diagram

Wiring-3 Contactor Wiring Diagram

Wiring-3 Contactor Auto-bypass Wiring Diagram

Technical Documents

Installation Materials-Honeywell SmartVFD HVAC LonWorks Protocol

Installation Materials-Honeywell SmartVFD Accessories: Door Keypad Mounting Kit

Application Guides-Variable Frequency Drive (VFD)

Product Data and Specifications-Honeywell SmartVFD HVAC SmartVFD HVAC Bypass Specification

Application Guides-Honeywell SmartVFD Installation and Application

Installation Materials-Honeywell SmartVFD HVAC Bypass Installation Instructions

Installation Materials-Honeywell SmartVFD Three Contactors and Three Contactors Auto-Bypass Installation Instruction

Product Data and Specifications-Honeywell SmartVFD HVAC Bypass Frame 5 Wiring Diagrams and Dimensional Drawings

Product Data and Specifications-Honeywell SmartVFD HVAC Bypass Frame 6 Wiring Diagrams and Dimensional Drawings

Product Data and Specifications-Honeywell SmartVFD HVAC Bypass Frame 4 Wiring Diagrams and Dimensional Drawings

Installation Materials-Honeywell SmartVFD Two Contactors Installation Instructions

Installation Materials-Honeywell SmartVFD Bypass Disconnect Installation Instructions

Installation Materials-SmartVFD HVAC Variable Frequency Drives for Variable Torque Applications

Modbus Protocol for Variable Frequency Drives

 



Назад в раздел