SmartVFD BYPASS, 208 Vac, 75 HP,Graphical, NEMA 12 Enclosure, Fused Disconnect Only || HVFDSB3A0750G210/U

Артикул: HVFDSB3A0750G210/U
Наименование: SmartVFD BYPASS, 208 Vac, 75 HP,Graphical, NEMA 12 Enclosure, Fused Disconnect Only
Производитель: Honeywell


Overview

The SmartVFD BYPASS is available in four configurations to meet your application needs: Disconnect Only, Two Contractor Bypass, Three Contractor Bypass, and Three Contractor with Auto-Bypass.

Features

  • Provides an economical means of bypassing the VFD
  • Freeze/Fire/Smoke Interlock
  • Fused Disconnect on some models
  • 3-Contactor bypass provides VFD isolation from power with motor running in BYPASS mode
  • 3-Contactor bypass provides TEST position powers the VFD without sending power to the motor
  • 3-Contactor Bypass with Auto-Bypass adds the control capabilities below to the standard three Contactor Bypass

Product Specifications

Dimensions (in.)
40.5 x 60 x 14
Dimensions (mm)
1028.7 x 1524 x 355.6
Weight (lb)
Contact Customer Care
Weight (kg)
Contact Customer Care
Frequency
0 Hz to 320 Hz
Voltage
208 Vac
Operating Temperature Range (F)
14 F to 122 F
Operating Temperature Range (C)
-10 C to 50 C
Enclosure
NEMA 12
Relay Outputs
Max. switching load: 250Vac/2A or 250Vdc/0,4A
Horsepower
75 HP
Current Ratings
205 A
Analog Current Output
0 (4) - 20 mA, max 500 ohm
Bypass
Drive with Fused Disconnect
Auto Bypass
No
Drive Family
SmartVFD HVAC
Disconnect Type
Fused
Drive Input Disconnect
Yes
Drive Input Fuses
Yes
Type of RFI Filter
EMC Filter
Continuous Output Current
overload 1.5 x High overload current (1min/10min), overload 1.1 x Low overload current (1min/10min)
Starting Torque
Depends on the Motor
Acceleration time
0.1 - 3000 sec
Deceleration time
.1 - 3000 sec
Analog Voltage Input
0 - 10 Vdc , 200K ohm
Analog Current Input
0 (4) - 20 mA, 250 ohm differential
Digital Output
Open collector, max. load 48V/50mA
Reference Output Voltage
Maximum Load 10mA
Auxiliary Voltage
? 20%, max. load 50 mA
Frame Type
8

Marketing Collateral

Sales/Promotional Materials-Commercial Field Devices

Sales/Promotional Materials-SmartVFD HVAC Bypass (Spanish)

Sales/Promotional Materials-Variable Frequency Drives - SmartVFD Selection Guide (Spanish)

Sales/Promotional Materials-SmartVFD HVAC and Bypass

Sales/Promotional Materials-Variable Frequency Drives - SmartVFD Selection Guide

Sales/Promotional Materials-SmartVFD HVAC and Bypass for Electrical Channel

Owners Manual

Operator/Owner Materials-Smart COMPACT VFD

Operator/Owner Materials-Honeywell SmartVFD BACnet Protocol Installation and UserТs manual

Wiring-Fused Disconnect Wiring Diagram

Wiring-Contactor Wiring Diagram

Wiring-3 Contactor Wiring Diagram

Wiring-3 Contactor Auto-bypass Wiring Diagram

Technical Documents

Installation Materials-Honeywell SmartVFD HVAC LonWorks Protocol

Installation Materials-Honeywell SmartVFD Accessories: Door Keypad Mounting Kit

Application Guides-Variable Frequency Drive (VFD)

Product Data and Specifications-Honeywell SmartVFD HVAC SmartVFD HVAC Bypass Specification

Application Guides-Honeywell SmartVFD Installation and Application

Installation Materials-Honeywell SmartVFD HVAC Bypass Installation Instructions

Installation Materials-Honeywell SmartVFD Three Contactors and Three Contactors Auto-Bypass Installation Instruction

Product Data and Specifications-Honeywell SmartVFD HVAC Bypass Frame 5 Wiring Diagrams and Dimensional Drawings

Product Data and Specifications-Honeywell SmartVFD HVAC Bypass Frame 6 Wiring Diagrams and Dimensional Drawings

Product Data and Specifications-Honeywell SmartVFD HVAC Bypass Frame 4 Wiring Diagrams and Dimensional Drawings

Installation Materials-Honeywell SmartVFD Two Contactors Installation Instructions

Installation Materials-Honeywell SmartVFD Bypass Disconnect Installation Instructions

Installation Materials-SmartVFD HVAC Variable Frequency Drives for Variable Torque Applications

Modbus Protocol for Variable Frequency Drives

 



Назад в раздел