Not available for purchase, If you need assistance please contact us sales@quad-industry.com Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com
Housing with removable, coded terminals
AS-Interface connection via Power Rail
Communication monitoring, turn-off
Outputs loadable up to 8 A (per module)
Addressing jack
Power supply of outputs from the external auxiliary voltage
Function display for bus, external auxiliary voltage and outputs
dual-LED green/red green: AS-Interface voltage, normal operation red: communication error or address 0
LED OUT
Switching state (output); 4 LED yellow
LED AE
ext. auxiliary voltage UAUX ; LED green
Electrical specifications
Auxiliary voltage (output)
20 ... 30 V DC PELV
Rated operating voltage
26.5 ... 31.6 V from AS-Interface
Rated operating current
≤ 30 mA
Protection class
III
Output
Number/Type
4 electronic outputs, PNP
Supply
from external auxiliary voltage UAUX
Current
2 A per output , 8 A per module
Voltage
≥ (UAUX - 0.5 V)
Programming instructions
Profile
S-8.F
IO code
8
ID code
F
Data bits (function via AS-Interface)
inputoutput
D0
-OUT1
D1
-OUT2
D2
-OUT3
D3
-OUT4
Parameter bits (programmable via AS-i)
function
P0
communication monitoring P0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition