Product Description |
G4 module IP67 4 inputs (2-wire ) |
General specifications |
Slave type | Standard slave |
AS-Interface specification | V2.0 |
Required master specification | ≥ V2.0 |
UL File Number | E87056 |
Indicators/operating means |
LED PWR | AS-Interface voltage; LED green |
LED IN | 4 dual LED yellow/red yellow: switching state (input) red: lead breakage red and yellow: line short-circuit |
Electrical specifications |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | ≤ 40 mA |
Protection class | III |
Input |
Number/Type | 4 inputs for 2-wire sensors, DC |
Supply | from AS-Interface |
Voltage | 15 V |
Input current | ≤ 8 mA (limited internally) |
Switching point | |
| 0 (unattenuated) | ≤ 1.5 mA |
| 1 (attenuated) | ≥ 4.5 mA |
Line fault detection | lead breakage: max. 0.5 mA lead short-circuit: min. 5 mA |
Programming instructions |
Profile | S-0.F |
IO code | 0 |
ID code | F |
Data bits (function via AS-Interface) | input output |
| D0 | IN1 - |
| D1 | IN2 - |
| D2 | IN3 - |
| D3 | IN4 - |
Parameter bits (programmable via AS-i) | function |
| P0 | lead monitoring IN1 P0 = 1 (basic setting), monitoring deactivated P0 = 0, monitoring activated |
| P1 | lead monitoring IN2 P1 = 1 (basic setting), monitoring deactivated P1 = 0, monitoring activated |
| P2 | lead monitoring IN3 P2 = 1 (basic setting), monitoring deactivated P2 = 0, monitoring activated |
| P3 | lead monitoring IN4 P3 = 1 (basic setting), monitoring deactivated P3 = 0, monitoring activated |
Compliance with standards and directives |
Standard conformity | |
| Protection degree | EN 60529 |
Ambient conditions |
Ambient temperature | -25 ... 60 В°C (-13 ... 140 В°F) |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
Mechanical specifications |
Protection degree | IP67 |
Connection | cable piercing method or terminal compartment yellow flat cable or standard round cable inputs: M12 x 1.5 cable gland and cage tension spring terminals |
Mass | 180 g |