Fieldbus interface |
Self current consumption | max. 6 mA (for version SCP-LBF-IA1.36.IE.1) , max. 0 mA (for version SCP-LBF-IA1.36.IE.0) |
Indicators/operating means |
LED ERR | green flashing: status OK , red flashing: maintenance required (for version SCP-LBF-IA1.36.IE.1) |
Electrical specifications |
Rated voltage | 36 V |
Rated current | 250 mA |
Voltage Protection Level | |
| Line/Line | max. 50 V category B2 10/700µsec , 25 A max. 53 V category C1 8/20µsec , 150 A max. 55 V category C2 8/20µsec , 150 A max. 46 V category C3 1kV/µsec , 10 A
|
| Line/Earth | max. 980 V category B2 10/700µsec , 50 A per line max. 800 V category C1 8/20µsec , 50 A per line max. 1450 V category C2 8/20µsec , 5 kA per line max. 1200 V category C3 1kV/µsec , 50 A per line max. 980 V category D1 10/350µsec , 500 A per line
|
| Screen/Shield indirect grounded (via GDT) | max. 500 V category B2 10/700µsec , 100 A max. 600 V category C1 8/20µsec , 500 A max. 700 V category C2 8/20µsec , 10 kA max. 550 V category C3 1kV/µsec , 100 A max. 570 V category D1 10/350µsec , 1 kA |
Reaction time | |
| Line/Line | max. 1 ns |
| Line/Earth | max. 100 ns |
| Screen/Shield-Earth | max. 100 ns |
Overstressed fault mode | acc. IEC 61643-21 line inoperable mode 2 |
Impulse durability | |
| Per line | 5 kA category C2 8/20µsec |
| Screen/Shield indirect grounded (via GDT) | 1 kA category D1 10/350µsec 10 kA category C2 8/20µsec |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
Standard conformity |
Electromagnetic compatibility | NAMUR NE 21 |
Protection degree | IEC 60529 |
Fieldbus standard | IEC 61158-2 |
Climatic conditions | IEC 60721 |
Shock resistance | EN 60068-2-27 |
Vibration resistance | EN 60068-2-6 |
Surge protection | IEC 61643-21 |
Ambient conditions |
Ambient temperature | -40 ... 70 В°C (-40 ... 158 В°F) |
Storage temperature | -40 ... 85 В°C (-40 ... 185 В°F) |
Relative humidity | ≤ 95 % non-condensing |
Shock resistance | 15 g 11 ms |
Vibration resistance | 1 g , 10 ... 150 Hz |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Connection type | screw terminals |
Core cross-section | flexible wire 2.5 mm2 solid wire max. 4 mm2 |
Housing material | Polyamide PA 6.6 |
Protection degree | IP20 |
Mass | pending |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate | SIRA 12 ATEX 2128X |
| Group, category, type of protection, temperature class | II 1G Ex ia IIC T4 |
| Voltage Ui | 24 V |
| Current Ii | 500 mA |
| Internal capacitance Ci | 2 nF |
| Internal inductance Li | 0.1 µH |
Statement of conformity | SIRA 12 ATEX 4176X |
| Group, category, type of protection, temperature class | II 3G Ex nAc IIC T4 , II 3G Ex ic IIC T4 |
| Voltage Ui | 33 V |
| Current Ii | 600 mA |
| Internal capacitance Ci | 2 nF |
Directive conformity | |
| Directive 94/9/EC | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 |
Supplementary information | FISCO field device |
International approvals |
CSA approval | pending |
| Control drawing | pending |
IECEx approval | IECEx SIR 12.0051X |
| Approved for | Ex ia IIC T4 |