Fieldbus interface |
Main cable (Trunk) | |
| Rated voltage | 9 ... 31 V DC 10.5 V DC minimum input voltage acc. to FF-846 |
| Rated current | max. 4.5 A |
Outputs | |
| Number of outputs | see table "Technical data depending on model" |
| Number of devices per output | 1 |
| Rated voltage | max. 31 V |
| Rated current | max. 32 mA switch 1, position 1 max. 43 mA switch 1, position 2 |
| Short-circuit current | 46 mA switch 1, position 1 65 mA switch 1, position 2 |
Self current consumption | see table "Technical data depending on model" |
Voltage drop main cable/outputs | max. 1.2 V |
Voltage drop trunk In/Out | 0 V |
Terminating resistor | external type M-FT 100 Ω +/- 10 % |
Surge protection | Trunk overvoltage protection if voltage exceeds typ. 39 V, max. 41 V |
Indicators/operating means |
Switch | configuration of short-circuit current/rated current |
LED PWR | green: Fieldbus voltage > 10 V and fieldbus terminator is deactivated |
LED COM/ERR | yellow: flashing: fieldbus communication status and physical layer diagnostic status |
LED SPURS | red: 2 Hz flashing in short-circuit condition |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
Standard conformity |
Electromagnetic compatibility | NE 21:2006 |
Protection degree | IEC 60529 |
Fieldbus standard | IEC 61158-2 |
Climatic conditions | IEC 60721 |
Shock resistance | EN 60068-2-27 |
Vibration resistance | EN 60068-2-6 |
Ambient conditions |
Ambient temperature | -50 ... 70 В°C (-58 ... 158 В°F) |
Storage temperature | -50 ... 85 В°C (-58 ... 185 В°F) |
Relative humidity | < 95 % non-condensing |
Shock resistance | 15 g 11 ms |
Vibration resistance | 1 g , 10 ... 150 Hz |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Connection type | removable screw terminals with retaining screws |
Core cross-section | max. 2.5 mm2 /AWG 12-24 |
Housing material | Polycarbonate |
Protection degree | IP20 |
Mass | see table "Technical data depending on model" |
Dimensions | see table "Technical data depending on model" |
Mounting | DIN rail mounting |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate | TГњV 12 ATEX 098651 X |
| Group, category, type of protection, temperature class | II 3 G Ex nAc [ic] IIC T4 |
Supply | |
| Maximum safe voltage | 35 V |
Outputs | |
| Voltage | 32 V |
| Current | 46 mA switch 1, position 1 65 mA switch 1, position 2 |
| Inductance | 0.25 mH switch 1, position 1 0.125 mH switch 1, position 2 |
| Capacitance | 60 nF |
Directive conformity | |
| Directive 94/9/EC | EN 60079-0:2009 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
IECEx approval | IECEx TUN 12.0015 X |
| Approved for | Ex nAc [ic] IIC T4 |
Certificates and approvals |
Marine approval | pending |