Segment Protector for Cabinet Installation | R2-SP-N* (Ex ic)

Артикул: R2-SP-N* (Ex ic)
Наименование: Segment Protector for Cabinet Installation | R2-SP-N* (Ex ic)
Производитель: Pepperl-Fuchs



  • 4 ... 12 outputs Ex ic, Ex nL (FISCO or Entity) or non-incendive (Div 2)
  • Short-circuit protection per output
  • Segment Protector in Zone 2/Div. 2
  • Instruments in Zone 2/Div. 2
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Power, Com, and Error LEDs
  • T-connector for easy installation and maintenance
  • Test points for easy troubleshooting

Datasheet as PDF in following languages:


Technical Data: R2-SP-N* (Ex ic)

Fieldbus interface
Main cable (Trunk)
Rated voltage9 ... 31 V DC
Rated currentmax. 4.5 A
Outputs
Number of outputssee table "Technical data depending on model"
Rated voltagemax. 31 V
Rated currentmax. 43 mA
Short-circuit currentmax. 58 mA
Self current consumptionsee table "Technical data depending on model"
Voltage drop main cable/outputsmax. 1.3 V
Voltage drop trunk In/Out0 V
Terminating resistorexternal type M-FT 100 Ω +/- 10 %
Surge protectionTrunk overvoltage protection if voltage exceeds typ. 39 V, max. 41 V
Indicators/operating means
LED ERRred: short-circuit
LED PWRgreen: Fieldbus voltage > 10 V
LED COMyellow: bus activity
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Standard conformity
Electromagnetic compatibilityNE 21:2006
Protection degreeIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-50 ... 70 В°C (-58 ... 158 В°F)
Storage temperature-50 ... 85 В°C (-58 ... 185 В°F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typeremovable screw terminals with retaining screws
Core cross-sectionmax. 2.5 mm2 /AWG 12-24
Housing materialPolycarbonate
Housing widthsee table "Technical data depending on model"
Housing heightsee table "Technical data depending on model"
Housing depthsee table "Technical data depending on model"
Protection degreeIP20
Masssee table "Technical data depending on model"
MountingDIN rail mounting
Data for application in connection with Ex-areas
Main cable (Trunk)
Rated currentsee Statement of Conformity
Outputs
Voltage24 V for IIC gas group, defined by trunk voltage
32 V for IIB gas group
Current65 mA for IIC and IIB gas groups
Inductance0.25 mH for IIC and IIB gas groups
Capacitance60 nF for IIC and IIB gas groups
Statement of conformityTГњV 11 ATEX 081151 X
Group, category, type of protection, temperature classEx-Hexagon II 3G Ex nA [nL] [ic] IIC T4
Directive conformity
Directive 94/9/ECEN 60079-0:2006 , EN 60079-11:2007 , EN 60079-15:2005 , EN 60079-27:2008
International approvals
FM approvalCoC 3027877, CoC 3027877C
Control drawingNo. 116-0280
Approved forClass I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, Ex nA [nL] IIC T4
UL approvalE106378
Approved forClass I, Division 2, Groups A, B, C, D
IECEx approvalIECEx 11.0011 X
Approved forEx-Hexagon Ex nA [nL] [ic] IIC T4
Certificates and approvals
Marine approvalDNV A-10798


Назад в раздел