Temperature Multi-Input Device for Cabinet Installation | RD0-TI-Ex8.FF.*

Артикул: RD0-TI-Ex8.FF.*
Наименование: Temperature Multi-Input Device for Cabinet Installation | RD0-TI-Ex8.FF.*
Производитель: Pepperl-Fuchs



  • For eight temperature or analog sensors
  • Installation in Zone 1...2/Div. 2, intrinsically safe
  • Sensors in Zone 0/Div. 1
  • Connection to fieldbus acc. to FISCO or Entity
  • For FOUNDATION Fieldbus H1
  • DCS integration via device description and function blocks
  • Concentrator method for simplified configuration
  • Monitors sensor condition
  • For T/C, RTD 2-, 3-, 4-wire, voltage and resistance
  • Cold junction compensation
  • Removable terminals

Datasheet as PDF in following languages:


Technical Data: RD0-TI-Ex8.FF.*

Fieldbus interface
Fieldbus typeFOUNDATION Fieldbus
Physical layer profileprofile type 511 (FISCO), profile type 111 (Entity)
ITK version4.51
Implementationresource block1x RS
function block8x AI, 1x MAI
transducer block8x sensor TB, 1x concentrator TB
Execution timeAI, MAI 40 ms max.
Macro cycletypical for one device 8xAI or 1xMAI max. 500 ms
Firmware updatevia separate plug connection
FDE (Fault Disconnect Equipment)6.7 mA
Polaritynot polarity sensitive
Rated voltage9 ... 32 V
Rated currentmax. 23 mA
Indicators/operating means
LED PWRgreen: on, bus voltage existent
LED COM ERRred: continuous lightning: hardware error; 2 Hz flashing: no bus activities or bus fault; off: no error
LED CHANNEL ERRORred: 2 Hz flashing: lead breakage, overrange; off: no error
Input
Number8
Sensor typessee table 1
Groundinggrounding of thermoelements possible
Error detectionlead breakage, wiring error, hardware device error
Common mode voltageInput to Input 600 Vpeak
Transfer characteristics
Deviation
LinearizationT/C input 0.1В°C RTD input 0.03В°C
Internal measurement cyclefor all sensor types max. 1 s
Electrical isolation
Fieldbus/inputssafe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Standard conformity
Electrical isolationEN 60079-11
Electromagnetic compatibilityNE 21:2006
Protection degreeIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 70 В°C (-40 ... 158 В°F) hazardous area
-40 ... 85 В°C (-40 ... 185 В°F) safe area
Storage temperature-40 ... 85 В°C (-40 ... 185 В°F)
Relative humidity≤ 95 % non-condensing
Shock resistance15 g
Vibration resistance5 g , 10 ... 150 Hz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typeplug-in terminals
Core cross-section
Busup to 2.5 mm2
Inputsup to 2.5 mm2
Housing materialPolycarbonate
Protection degreeIP20
Mass360 g
Mountingmounting on DIN rail in cabinet
Data for application in connection with Ex-areas
EC-Type Examination CertificatePTB 03 ATEX 2237
Group, category, type of protection, temperature classEx-Hexagon II 2(1G/D) G Ex ia IIC T4 , Ex-Hexagon II (1)GD [Ex ia] IIC
BusFISCO see EC-Type Examination Certificate
Inputssee EC-Type Examination Certificate
Statement of conformityPTB 03 ATEX 2238 X
Group, category, type of protection, temperature classEx-Hexagon II 3G Ex nA II T4 , Ex-Hexagon II 3G Ex nL IIC T4 , Ex-Hexagon II (3)G [Ex nL] IIC
Electrical isolation
Bussee Statement of Conformity
Inputsee EC-Type Examination Certificate
Directive conformity
Directive 94/9/ECEN 60079-0:2006 , EN 60079-11:2007 , EN 60079-15:2005 , EN 60079-27:2006


Назад в раздел