Fieldbus interface |
PROFIBUS PA | |
| Connection | Connection +, - |
| Rated voltage | 9 ... 32 V |
| Rated current | max. 23 mA |
| Baud rate | 31.25 kBit/s |
| Protocol | PROFIBUS DP V1 |
| Terminal "S" | only for the connection of the cable screen (BUS) and/or the potential compensation |
| Terminal "PA" | only for the connection of the cable screen (sensor interface) and/or grounding |
| Grounding plate | only for the connection of the potential compensation |
Field circuit |
Inputs | |
| Connection | 4, for binary sensors: terminals 1+, 2-, 5+, 6-, 9+, 10-, 13+, 14- 8, for binary sensors: terminals 3, 4, 7, 8, 11, 12, 15, 16 |
| Sensor supply voltage | 4, for binary sensors: 5.5 V 8, for binary sensors: 5 V |
| Sensor supply current | 4, for binary sensors: 4.5 mA 8, for binary sensors: ≤ 5 mA |
| Time delay before availability | for 4 binary sensors, 1 s for 8 binary sensors, < 3 ms |
| Max. cycle time | for binary 4 sensors, 4 x 1 s = 4 s for 8 binary sensors, 8 x 12.5 ms = 100 ms |
Electrical isolation |
PROFIBUS PA/Field circuit | safe galvanic isolation acc. to EN 50020, voltage peak value 60 V |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
Standard conformity |
Electrical isolation | EN 50178 |
Electromagnetic compatibility | NE 21:2006 |
Protection degree | IEC/EN 60529 |
Fieldbus standard | EN 50170/2 |
Ambient conditions |
Ambient temperature | -20 ... 70 В°C (-4 ... 158 В°F) |
Storage temperature | -40 ... 85 В°C (-40 ... 185 В°F) |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Core cross-section | Bus cable:∅ 5 mm ... 10 mm cable sensors: ∅ 4 mm ... 8 mm |
Housing | 187 mm x 129 mm x 46 mm |
Protection degree | IP65 |
Installation position | Cable glands downwards |
Mass | approx. 290 g |
Mounting | panel mounting |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate | PTB 98 ATEX 2210 |
| Group, category, type of protection, temperature class | II (1)2G EEx ia IIC T4 |
PROFIBUS PA | |
| Voltage | 24 V |
| Current | 380 mA |
| Power | 5.32 W |
| FDE (Fault Disconnect Equipment) | 6.7 mA |
| Terminal "S" | only for the connection of the cable screen (BUS) and/or the potential compensation |
| Terminal "PA" | only for the connection of the cable screen (sensor interface) and/or grounding |
| Grounding plate | only for the connection of the potential compensation |
Field-side | |
| Voltage Uo | 9 V |
| Current Io | 44 mA |
| Power Po | 99 mW |
Directive conformity | |
| Directive 94/9/EC | EN 50014:1997 EN 50020:1994 |
International approvals |
FM approval | 3009604 |
| Control drawing | No. 116-0259 |
| Approved for | IS Class I, Division 1, Groups A, B, C, D / Class I, Zone 0, AEx ia IIC T4 |
IECEx approval | IECEx TUN 04.0002 |
| Approved for | Ex ia IIC T4 |