WirelessHART Adapter | WHA-ADP-F8B2-*-P*-Z1(-Ex1)

Артикул: WHA-ADP-F8B2-*-P*-Z1(-Ex1)
Наименование: WirelessHART Adapter | WHA-ADP-F8B2-*-P*-Z1(-Ex1)
Производитель: Pepperl-Fuchs



  • 1-channel
  • Installation in Zone 1
  • WirelessHART Adapter
  • Battery operated
  • Also supplies field device
  • Input 2-wire HART transmitters and 2-wire HART current sources
  • Output WirelessHART wireless interface
  • Direct mounting on HART- or 4 mA ... 20 mA field device
  • Rotatable antenna

Datasheet as PDF in following languages:


Technical Data: WHA-ADP-F8B2-*-P*-Z1(-Ex1)

Supply
Rated voltage7.2 V DC , battery operated
Electrical specifications
Output rated operating current4 ... 20 mA
Supplyloop power for field devices
voltage 8 ... 23 V DC, adjustable in steps of 0.1 V
Input
Connectable field devicesusable for:
- one point-to-point connection with a HART field device, or
- one point-to-point connection with a 4 ... 20 mA field device, or
- up to four externally powered HART field devices operating in multidrop mode
Connectionterminals 1, 2, 3, 4, 5, 6
multiple wirings available , depending on operating mode
Current4 ... 20 mA
HART communication
ProtocolHART 7.1, backward compatible
Number of devices- one passive 4 ... 20 mA/HART field device
- up to 4 HART field devices in multidrop mode
Transfer rate1200 Bit/s
Parametersprimary/secondary master, preambles, retries and short address scan ranges
Output
Output variablesPV: loop current
SV, TV, QV:configurable according to user requirement
- adapter: temperature, battery voltage, energy consumed and estimated battery life-time
- 4 ... 20 mA device: scaled or linearized process value
- HART device: up to four process variables
Transfer characteristics
Accuracycurrent input: 0.125 % of measuring range
Influence of ambient temperaturecurrent input: 5 µA/K
Indicators/settings
Parameter assignment- wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP)
- device variables mapping
- publishing of up to ten burst messages in a wireless network, period and trigger mode selectable
- notification of up to five events from adapter and/or connected device(s) in a wireless network
- scaling and linearization of 4 ... 20 mA signal of connected analog device
- tuning of supply parameters for the connected device
- locking/unlocking of device parameterization
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Radio and telecommunication terminal equipmentThe usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning.
Directive 99/5/ECETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001
FCC CFR47 Part 15 B and CANSI C63.4-2003
Conformity
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-40 ... 60 В°C (-40 ... 140 В°F)
Storage temperature-40 ... 85 В°C (-40 ... 185 В°F)
Vibration resistance20 ... 2000 Hz, 0,01 g2/Hz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
test setup and execution acc. to EN 60068-2-60
Mechanical specifications
Protection degreeIP66
Materialplastic
Massapprox. 750 g
Dimensions91 x 88.5 x 100.6 mm (3.6 x 3.5 x 4 in) (without cable glands and antenna)
Mountingmounting on field device , panel or pole mounting
versions see type code
Data for application in connection with Ex-areas
EC-Type Examination CertificateBVS 11 ATEX E 081 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection, temperature classEx-Hexagon II 2 G Ex ia IIC T4 Gb
Directive conformity
Directive 94/9/ECEN 60079-0:2009 , EN 60079-11:2007 , EN 60079-31:2009
International approvals
IECEx approvalBVS 11.0061


Назад в раздел