General specifications |
Signal type | Digital Output |
Supply |
Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
Rated voltage | 20.4 ... 30 V via Termination Board |
Input current | 65 mA at 24 V, 300 Ω load (per channel) |
Power loss | 1.1 W at 24 V, 300 Ω load (per channel) |
Input |
Connection | SL1: 8a(+), 7a(-); 10a(+), 9a(-) |
Control input | external switch (dry contact or open collector) non isolated or logic signal input fully floating |
Operating mode | output on with contact close or transistor on or logic level > 4 V output off with contact open or transistor off or logic level < 1.5 V |
Output |
Connection | SL2: 5a(+), 5b(-); 1a(+), 1b(-) |
Output voltage | 40 mA at 12 V DC, 52 mA current limit |
Load | 0.1 ... 5 kΩ |
Switching frequency | max. 250 Hz |
Response time | turn-on time 1 ms, turn-off time 2 ms, at 300 Ω load |
Error message output |
Connection | SL1: 6b |
Output type | open collector transistor (internal fault bus) |
Fault current | 4 mA typical |
Fault level | lead short-circuit detection at < 25 Ω lead breakage detection at > 100 kΩ typical |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
Conformity |
Electromagnetic compatibility | NE 21:2006 For further information see system description. |
Protection degree | IEC 60529 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree | IP20 |
Mass | approx. 140 g |
Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 in) |
Mounting | on Termination Board |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate | CESI 02 ATEX 086 , for additional certificates see www.pepperl-fuchs.com |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC |
Directive conformity | |
| Directive 94/9/EC | EN 60079-0:2009, EN 60079-11:2007 , EN 60079-26:2007 , EN 61241-11:2006 |
International approvals |
CSA approval | |
| Control drawing | 366-005CS-12B (cCSAus) |