Frequency current converter with trip value and direction of rotation | KFU8-UFT-Ex2

Артикул: KFU8-UFT-Ex2
Наименование: Frequency current converter with trip value and direction of rotation | KFU8-UFT-Ex2
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • 2 inputs
  • Control circuit EEx ia IIC
  • Input frequency 1 mHz ... 5 kHz
  • Analog output 0/4 mA ... 20 mA
  • Measuring range parameterisable
  • 2 relay outputs
  • 2 electronic outputs, isolated
  • Each output individually parameterisable as trip value, serially switched output, direction of rotation, synchronization monitoring or error message output
  • Start-up override
  • Lead breakage (LB) and short-circuit (SC) monitoring
  • Bounce filter
  • Parameterization via PC or control panel (optional)

Datasheet as PDF in following languages:


Technical Data: KFU8-UFT-Ex2

Product Description
48 V AC ... 253 V AC/20 V DC ... 90 V DC
Supply
Connectionterminals 23, 24
Rated voltage20 ... 90 V DC / 48 ... 253 V AC
Power loss2.2 W / 3.5 VA
Power consumption2.5 W / 4 VA
Input
Connectioninput I: terminals 1+, 3-
input II: terminals 4+, 6-
start-up override I: terminals 13+, 14-
start-up override II: terminals 15+, 14-
Functionreset:
rotation direction signaling: reset in preferred direction (left-hand rotation)
slip monitoring: reset slip error
hold:
slip monitoring: if the input is bridged, the Hold function becomes active. Lead fault is only indicated by relay 2 and combined fault indication. The condition of the relay is hold during fault.
Input I, IIacc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current8.2 V / 10 mA
Pulse durationmin. 200 µs overlapping by rotation direction signaling: ≥ 100 µs
Input frequencyrotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
Lead monitoringbreakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input III, IV
Active/PassiveI > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit current18 V / 5 mA
Output
Connectionoutput I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 19+, 20-
output IV: terminals 21+, 20-
Output I, IIsignal , relay
Contact loading250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
Mechanical life5 x 107 switching cycles
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Output III and IVsignal , electronic output, passive
Contact loading40 V DC
Signal level1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof)
0-signal: switched off (off-state current ≤ 10 µA)
Programming interface
Connectionprogramming socket
InterfaceRS 232
Directive conformity
Electromagnetic compatibility
Directive 89/336/EECEN 61326, EN 50081-2, NE 21
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Mechanical specifications
Protection degreeIP20
Mass300 g
Data for application in connection with Ex-areas
EC-Type Examination CertificateTГњV 99 ATEX 1471
Group, category, type of protectionEx-Hexagon II (1)GD [EEx ia] IIC
Directive conformity
Directive 94/9/ECon request


Назад в раздел