Signal Converter | KFD2-TR-Ex1

Артикул: KFD2-TR-Ex1
Наименование: Signal Converter | KFD2-TR-Ex1
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • 1-channel
  • Input EEx ia IIC
  • 24 V DC supply voltage
  • Current output: 0/4 mA ... 20 mA (optional voltage output)
  • Accuracy ± 0.1 %
  • User can use DIP switch to adjust: Temperature measuring range, measuring sensor, 2-, 3- or 4-wire connection, lead breakage monitoring
  • Output: 0/4 mA ... 20 mA (adjustable)

Datasheet as PDF in following languages:


Technical Data: KFD2-TR-Ex1

Supply
ConnectionPower Rail or terminals 23+, 24-
Rated voltage20 ... 35 V DC
Ripplewithin the supply tolerance
Power consumptionapprox. 1.2 W
Input
Connectionterminals 1, 2, 3; 7, 8, 9 designed for the connection of a resistance temperature sensor in 2, 3 or 4-wire technology according to BS1904: 1981 (IEC 751) or DIN 43760 (e. g. Pt100)
Line fault detectionbreakage: upscale or downscale (selectable)
Output
Connectionterminals 16-, 17+, 18-
Current0/4 ... 20 mA, load ≤1 kOhm
Voltage0 ... 20 V ; ≥ 30 kΩ load at error < 1 %
Transfer characteristics
Rise time300 ... 700 ms , dependent on temperature measurement probe used
Directive conformity
Electromagnetic compatibility
Directive 89/336/EECEN 50081-2, EN 50082-2
Conformity
Insulation coordinationEN 50178
Electrical isolationEN 50178
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Mechanical specifications
Protection degreeIP20
Massapprox. 150 g
Dimensions40 x 107 x 115 mm (1.6 x 4.2 x 4.5 in)
Data for application in connection with Ex-areas
EC-Type Examination CertificateBASEEFA No. Ex 91C2043 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection[EEx ia] IIC (Tamb = 60 В°C)
Directive conformity
Directive 94/9/ECEN 50014, EN 50020