Артикул: KFD2-UT-Ex1-1
Наименование: Signal Converter | KFD2-UT-Ex1-1
Производитель: Pepperl-Fuchs
Not available for purchase, If you need assistance please contact us sales@quad-industry.com Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com
1-channel
Input EEx ia IIC
24 V DC supply voltage
Accuracy ± 0.1 %
Adjustment option of temperature measuring range for Pt100, Ni100 in 2-, 3- or 4-wire versions
Adjustment option of thermocouple (B, E, J, K, L, N, R, S or T)
Freely definable characteristic curve for resistance 0 Ω ... 400 Ω and voltage -50 mV ... +150 mV
Internal/External cold junction compensation
Sensor burnout monitoring for thermocouples
Sensor burnout and short-circuit monitoring (SC) for Pt100
terminals 1, 2, 3 and 4 suitable for Pt100, Ni100, thermocouples type B, E, J, K, L, N, R, S or T (IEC 584) configuration via programming jack
Lead resistance
max. 50 Ω per lead
Measuring current
approx. 400 µA with resistance measuring sensor current for lead breakage monitoring switched off during the measurement
Output
Voltage output
1 ... 5 V ; 5.125 V at input signal overrange fault message: downscale 0.5 ... 1 V or upscale 5.025 ... 5.125 V (programmable) output resistance: ≤ 10 Ω ; load: ≥ 10 kΩ
Connection
terminals 7-, 8+
Transfer characteristics
Reaction time
≤ 430 ms
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC
EN 61326-1:2006
Conformity
Insulation coordination
EN 50178
Electrical isolation
EN 50178
Electromagnetic compatibility
NE 21
Protection degree
IEC 60529
Ambient conditions
Ambient temperature
-20 ... 60 В°C (-4 ... 140 В°F)
Mechanical specifications
Protection degree
IP20
Mass
approx. 110 g
Dimensions
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in)
Data for application in connection with Ex-areas
EC-Type Examination Certificate
BAS 01 ATEX 7256 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection
II (1)GD [EEx ia] IIC (-20 В°C ≤ Tamb ≤ 60 В°C)
Statement of conformity
TГњV 02 ATEX 1797 X (observe statement of conformity)
Group, category, type of protection, temperature class