Not available for purchase, If you need assistance please contact us sales@quad-industry.com Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com
at 20 mA: approx. 16.5 V at 200 Ohm Output load dependent on output load: U = 19.65 - (16.5 x 10-3 x RB); with RB = output load in Ohm
Output
Connection
terminals 8-, 9+, 10-, 11+
Output signal
4 ... 20 mA , max. load 500 Ohm, with HART ≥ 230 Ohm
Ripple
max. 75 µA ss
Transfer characteristics
Deviation
≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
Frequency range
field side into the control side: bandwidth with 1 mApp signal 0 ... 40 kHz (-1 dB); 0 ... 100 kHz (-6 dB) safe area to hazardous area: band width with 1 VSS signal 0 ... 40 kHz (-1 dB); 0 ... 100 kHz (-6 dB)
Rise time
40 µs
De-energized delay
40 µs
Directive conformity
Electromagnetic compatibility
standards
Directive 89/336/EEC
EN 61326, EN 50081-2, NE 21
Ambient conditions
Ambient temperature
-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degree
IP20
Mass
approx. 150 g
Data for application in connection with Ex-areas
EC-Type Examination Certificate
BAS 00 ATEX 7127 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection
II (1)GD [EEx ia] IIC (Tamb = -20 °C to +60 °C) [circuit(s) in zone 0/1/2]