Product Description |
Input 0/4 mA ... 20 mA 2 x Output 4 mA ... 20 mA (current sink) |
Supply |
Connection | Power Rail or terminals 14+, 15- |
Rated voltage | 20 ... 35 V DC |
Ripple | within the supply tolerance |
Power loss | 1.6 W |
Power consumption | 2.5 W |
Input |
Connection | terminals 1, 2, 3 or 5-, 6+ |
Input signal | 0/4 ... 20 mA |
Input resistance | max. 76 Ω terminals 2-, 3 |
Available voltage | ≥ 15.7 V at 20 mA terminals 1+, 3 |
Output |
Connection | terminals 7+, 8-; 10+, 11- |
Output signal | 0/4 ... 20 mA (overload > 25 mA) |
Ripple | max. 50 µA rms |
External supply (loop) | 30 V DC |
Transfer characteristics |
Deviation | at 20 °C (68 °F), 0/4 ... 20 mA ≤ 20 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB) |
Directive conformity |
Electromagnetic compatibility | |
| Directive 89/336/EEC | EN 61326, EN 50081-2, EN 50082-2 |
Conformity |
Insulation coordination | EN 50178 |
Electrical isolation | EN 50178 |
Electromagnetic compatibility | NE 21 |
Protection degree | IEC 60529 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree | IP20 |
Mass | approx. 100 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate | BAS 99 ATEX 7060 , for additional certificates see www.pepperl-fuchs.com |
| Group, category, type of protection | II (1)G [EEx ia] IIC (-20 °C ≤ Tamb ≤ 60 °C) |
Statement of conformity | TUV 99 ATEX 1499 X , observe statement of conformity |
| Group, category, type of protection, temperature class | II 3G EEx nA II T4 |
Directive conformity | |
| Directive 94/9/EC | EN 50014, EN 50020, EN 50021 |