Transmitter Power Supply | KFD2-CR-Ex1.20200

Артикул: KFD2-CR-Ex1.20200
Наименование: Transmitter Power Supply | KFD2-CR-Ex1.20200
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • 1-channel
  • Input EEx ia IIC; Uo = 20V, use standard type KFD2-STC4-Ex1 with Uo = 25.2 V
  • 24 V DC supply voltage
  • Output: allowable load max. 1 kΩ
  • EMC acc. to NAMUR NE 21

Datasheet as PDF in following languages:


Technical Data: KFD2-CR-Ex1.20200

Supply
ConnectionPower Rail or terminals 11+, 12-
Rated voltage20 ... 35 V DC
Ripple< 20 µAeff
Power loss1.1 W
Power consumptionmax. 1.6 W
Input
Connectionterminals 1+, 3-
Available voltage≥ 16 V DC at 20 mA
Output
Open loop voltage20 V DC
Connectionterminals 7-, 8+, 9-
Load≤ 1 kΩ
Output signal4 ... 20 mA
Ripplemax. 20 µA ss
Transfer characteristics
Rise timeapprox. 50 µs
Directive conformity
Electromagnetic compatibility
Directive 89/336/EECEN 61326, EN 50081-2
Conformity
Electromagnetic compatibilityEN 50081-2, EN 50082-2, NE 21, IEC 801-4, 801-5 and 801-6, intensity level 3
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degreeIP20
Massapprox. 100 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in)
Data for application in connection with Ex-areas
EC-Type Examination CertificateBAS 00 ATEX 7164 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1)GD [EEx ia] IIC (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2]
Statement of conformityTUV 02 ATEX 1797 X , observe statement of conformity
Group, category, type of protection, temperature classEx-Hexagon II 3G EEx nA II T4 [device in zone 2]
Directive conformity
Directive 94/9/ECEN 50014, EN 50020, EN 50021