Transmitter Power Supply | KFU8-CRG-Ex1.D

Артикул: KFU8-CRG-Ex1.D
Наименование: Transmitter Power Supply | KFU8-CRG-Ex1.D
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • 1-channel isolated barrier
  • Universal usage at different power supplies
  • 2-wire transmitters or current sources
  • Output 0/4 mA ... 20 mA
  • 2 relay contact outputs
  • Programmable high/low alarm
  • Configurable by PACTwareTM or keypad
  • Line fault detection (LFD)
  • Up to SIL2 acc. to IEC 61508

Datasheet as PDF in following languages:


Technical Data: KFU8-CRG-Ex1.D

Product Description
48 V AC ... 253 V AC/20 V DC ... 90 V DC
Supply
Connectionterminals 23, 24
Rated voltage20 ... 90 V DC or 48 ... 253 V AC
Power loss2 W / 3 VA
Power consumption2.2 W / 4 VA
Input
Connectionterminals 1, 2, 3
Input I
Input signal0 ... 20 mA or 4 ... 20 mA
Available voltage> 15 V at 20 mA
Open circuit voltage/short-circuit current24 V / 33 mA
Input resistance45 Ω (terminals 2, 3)
Lead monitoringbreakage I < 0.2 mA; short-circuit I > 22 mA acc. to NAMUR NE43
Output
Connectionoutput I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 8+, 7-
Output signal0 ... 20 mA or 4 ... 20 mA
Output I, IIsignal, relay
Contact loading250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
Mechanical life5 x 107 switching cycles
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Output IIISignal, analog
Current range0 ... 20 mA or 4 ... 20 mA
Open loop voltagemax. 24 V DC
Loadmax. 650 Ω
Fault signaldownscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Directive conformity
Electromagnetic compatibility
Directive 89/336/EECEN 61326, EN 50081-2, EN 50082-2
Low voltage
Directive 73/23/EECEN 50178
Conformity
Insulation coordinationEN 50178
Electrical isolationEN 50178
Electromagnetic compatibilityNE 21
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Mechanical specifications
Protection degreeIP20
Mass300 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) , housing type C3
Data for application in connection with Ex-areas
EC-Type Examination CertificateTГњV 01 ATEX 1701 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2]
Directive conformity
Directive 94/9/ECEN 50014, EN 50020
International approvals
CSA approval
Control drawing116-0202