PS3500 Power Supply Backplane - 6-position | PS3500-TB-6

Артикул: PS3500-TB-6
Наименование: PS3500 Power Supply Backplane - 6-position | PS3500-TB-6
Производитель: Pepperl-Fuchs



  • 6-position backplane for PS2500/PS3500 series power modules
  • Multiple input/output wiring configurations
  • Removable terminals for easy wiring
  • Serial or parallel fault bus
  • ATEX and cULus approvals for Div 2/Zone 2

Datasheet as PDF in following languages:


Technical Data: PS3500-TB-6

Product Description
6 position N+1 Power Supply Backplane for use with PS2500 and PS3500 N+1 Power Supplies.
Interface
Typediagnostic bus: RS 485
Input
Rated valuesterminal ratings: current 30 A, voltage 300 V
Output
Fault signalremovable terminals : power module alarm
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
EN 61000 sections 3-2, 3-3, 4-2, 4-4, 4-5, 4-6, and 4-11
Conformity
Electromagnetic compatibilityNE 21:2006
Protection degreeEN 60529
Ambient conditions
Ambient temperature-25 ... 70 В°C (-13 ... 158 В°F)
Storage temperature-40 ... 85 В°C (-40 ... 185 В°F)
Vibration resistance1 g , 58 ... 150 Hz
Mechanical specifications
Core cross-sectioninput terminals: 4 mm2 (10 AWG)
output terminals: 10 mm2 (6 AWG)
Housing materialPowder Coated, 1010 Cold Rolled Steel
Protection degreeIP20
Massapprox. 2.9 kg ( 6.375 lbs )
Dimensions193 x 78 x 486 mm (7.6 x 3.1 x 19.1 in)
Data for application in connection with Ex-areas
EC-Type Examination CertificateITS 09 ATEX 46140 X
Group, category, type of protectionEx-Hexagon II3 G Ex nC IIC T4
Directive conformity
Directive 94/9/ECEN 60079-0, EN 60079-15
International approvals
UL approvalcULus Listed
E230669
E350173
Approved forClass I/Div 2, ABCD
ETL Interteklisted
ANSI/UL 508 - 2005
ANSI/ISA 12.12.01 - 2.07
CSA C22.2 No. 213
C22.2 No.214CSA C22.2 No. 213
CAN/CSA C22.2 No.14-05
With update No.3, 2008
Approved forClass I, Zone 2, Group IIC T4
Class I, Division 2, Groups A, B, C, D, T4


Назад в раздел