Backplane bus isolator | RSD2-ISO-Ex.Slave

Артикул: RSD2-ISO-Ex.Slave
Наименование: Backplane bus isolator | RSD2-ISO-Ex.Slave
Производитель: Pepperl-Fuchs



  • For the simultaneous connection of non-intrinsically safe and intrinsically safe field signals to one IS-RPI system
  • Non-intrinsically safe/intrinsically safe isolation of the internal backplane bus
  • Satisfies the European standard 94/9 EG
  • Satisfies the US standard NEC 500

Datasheet as PDF in following languages:


Technical Data: RSD2-ISO-Ex.Slave

Supply
Connectionterminals V+, V-
Rated voltage18 ... 32 V DC
Ripplemax. 10 %
Rated current150 mA
Power loss2.2 W
Internal bus
Interfacemanufacturer specific bus
Output
Connectionintrinsically safe backplane bus
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Explosion protection
Directive 94/9/ECEN 60079-0: 2006, EN 60079-11: 2007 , EN 61241-0: 2006, EN 61241-11: 2006
Standard conformity
Insulation coordinationEN 50178
Electrical isolationEN 60079-11:2007
Electromagnetic compatibilityNE 21:2006
Protection degreeIEC 60529
Climatic conditionsDIN IEC 721
Ambient conditions
Classification3K3
Ambient temperature-20 ... 70 В°C (-4 ... 158 В°F)
Storage temperature-20 ... 100 В°C (-4 ... 212 В°F)
Relative humidity95 % non-condensing
Shock resistance30 g peak, 11 ms period
Vibration resistance5 g , 10 ... 500 Hz according to IEC 60068-2-6
Damaging gasacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typeTerminals
Protection degreeIP20, for on-site installation a separate housing is required with a minimum of IP54
Massapprox. 265 g
MountingDIN rail mounting
Data for application in connection with Ex-areas
EC-Type Examination CertificateDMT 00 ATEX E 055 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (2)G [Ex ib] IIC
Ex-Hexagon II (2)D [Ex ibD]
Supply18 ... 32 V DC
Maximum safe voltage253 V AC
Output
External capacitance39 µF
External inductance100 µH
Voltage5.75 V
Current400 mA
Power2.05 W
Internal buscustomer specific
Declaration of conformity
Group, category, type of protection, temperature classEx-Hexagon II 3G Ex nA IIC T4
Electrical isolation
Internal bus/power supplysafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Output/power supplysafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Output/Internal Bussafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V


Назад в раздел