HART Transmitter Power Supply, Input Isolator | FB3203B

Артикул: FB3203B
Наименование: HART Transmitter Power Supply, Input Isolator | FB3203B
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • 1-channel
  • Input Ex ia
  • Power supply for 2- or 3-wire transmitters with 4 mA ... 20 mA
  • Supply circuit 15 V (20 mA)
  • Input from active signals of 4-wire transmitters
  • Installation in suitable enclosures in Zone 1 or Zone 21
  • HART communication via field bus or service bus
  • HART communication also for separately powered devices
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD) and Live Zero monitoring
  • Permanently self-monitoring

Datasheet as PDF in following languages:


Technical Data: FB3203B

Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies FB92**
Power consumptionapprox. 1.2 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer specific bus to standard com unit/bus coupler
Input
Number of channels1
Suitable field devicestransmitters for pressure, differential pressure, level, flow, temperature, etc.
Connectionterminals 2+, 5-: HART supply; 5+, 6-: input; 1+, 6-: HART input
Input resistance15 Ω (terminals 5, 6)
236 Ω (terminals 1, 6) , HART
Transmitter supply voltagemin. 15 V at 20 mA (incl. 250 Ω HART communication resistor)
Line fault detectionParameterization range 0 ... 26 mA
Ex works settings: line fault < 0.5 mA, short circuit > 22 mA
Live Zero monitoringEx works settings: max. 3.6 mA
Transfer characteristics
Deviation0.1 % of the input signal range at 20 В°C (68 В°F)
Resolution12 Bit (0 ... 26 mA)
Refresh timeapprox. 50 ms
Indicators/settings
LED indicatorLED green: supply
LED red: line fault
LED yellow: signal (Live Zero status)
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1
Conformity
Electromagnetic compatibilityNE 21
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100
Vibration resistancefrequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ± 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz
Damaging gasfor plugs: 21 days in 25 ppm SO2, at 25 В°C and 75 % rel. humidity, device G3
Mechanical specifications
Protection degreeIP20 (module) , a separate housing is required acc. to the system description
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Massapprox. 350 g
Dimensions28 x 107 x 132 mm (1.1 x 4.2 x 5.2 in)
Data for application in connection with Ex-areas
EC-Type Examination CertificatePTB 97 ATEX 1074 U , PTB 97 ATEX 1075 (system) , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II 2(1) G Ex d [ia] IIC , [Ex iaD]
Supply
Voltage24.9 V
Current77 mA
Power478 mW (linear characteristic)
Connection 1-6
Voltage8.9 V
Current56 mA
Power336 mW (trapezoid characteristic curve)
Input
Voltage0.7 V
Current3 mA
Power2 mW (trapezoid characteristic curve)
Electrical isolation
Input/power supply, internal bussafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/ECEN 60079-0, EN 60079-1, EN 60079-11, EN 60079-26, EN 61241-0, EN 61241-11
International approvals
IECEx approvalpending


Назад в раздел