HART Transmitter Power Supply, Input Isolator | FB3305*

Артикул: FB3305*
Наименование: HART Transmitter Power Supply, Input Isolator | FB3305*
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • 4-channel
  • Inputs wired to Ex e terminals
  • Power supply for 2- or 3-wire transmitters with 4 mA ... 20 mA
  • Supply circuit 15 V (20 mA)
  • Input from active signals of 4-wire transmitters
  • Installation in suitable enclosures in Zone 1 or Zone 21
  • HART communication via field bus or service bus
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD)
  • Permanently self-monitoring

Datasheet as PDF in following languages:


Technical Data: FB3305*

Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies FB92**
Power consumption3 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer specific bus to standard com unit/bus coupler
Input
Number of channels4
Suitable field devicestransmitters for pressure, differential pressure, level, flow, temperature, etc.
Connectionwire ends 1+ (white), 2- (brown), 5+ (grey), 6- (pink), 9+ (white), 10- (brown), 13+ (grey), 14- (pink) HART supply circuit
wire ends 3+, 4- / 7+, 8- / 11+, 12- / 15+, 16- active field devices
Input resistance15 Ω (stat.) , no HART for separately powered field devices
Transmitter supply voltagemin. 15 V at 20 mA
Line fault detectionParameterization range 0 ... 26 mA
Ex works settings: line fault < 0.5 mA, short circuit > 22 mA
Transfer characteristics
Deviation0.1 % of the input signal range at 20 В°C (68 В°F)
Resolution12 Bit (0 ... 26 mA)
Refresh timeapprox. 80 ms (4 channels)
130 ms during HART
Indicators/settings
LED indicatorLED green: supply
LED green flashing: calibration error
LED red: line fault
Red LED, flashing communication error
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1
Conformity
Electromagnetic compatibilityNE 21
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100
Vibration resistancefrequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ± 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz
Damaging gasfor plugs: 21 days in 25 ppm SO2, at 25 В°C and 75 % rel. humidity, device G3
Mechanical specifications
Protection degreeIP20 (module) , a separate housing is required acc. to the system description
Connectionwire ends or shielded cable tail
wiring connection: separately covered Ex e terminals required
Massapprox. 750 g
Dimensions57 x 107 x 132 mm (2.2 x 4.2 x 5.2 in)
Data for application in connection with Ex-areas
EC-Type Examination CertificatePTB 97 ATEX 1074 U , PTB 97 ATEX 1075 (system) , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II 2 G Ex d IIC
Electrical isolation
Input/power supply, internal bussafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/ECEN 60079-0 , EN 60079-1
International approvals
IECEx approvalpending


Назад в раздел