Digital Input | FB1308*

Артикул: FB1308*
Наименование: Digital Input | FB1308*
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • 8-channel
  • Inputs wired to Ex e terminals
  • Dry contact or NAMUR inputs
  • Installation in suitable enclosures in Zone 1 or Zone 21
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD)
  • Permanently self-monitoring
  • On/Off delay

Datasheet as PDF in following languages:


Technical Data: FB1308*

Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies FB92**
Power consumption0.7 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer specific bus to standard com unit/bus coupler
Input
Number of channels8
Suitable sensorsmechanical contacts, NAMUR proximity switches, 2-wire initiators
Connectionwire ends 1/9+ (white), 2/10- (brown), 3/11+ (green), 4/12- (yellow), 5/13+ (grey), 6/14- (pink), 7/15+ (blue), 8/16- (red)
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Switching point/switching hysteresis1.2 ... 2.1 mA / ± 0.2 mA
Line fault detectionoption: On/Off, for each channel
mechanical switches: see connection diagram
NAMUR proximity switches: no replacement network required
switching points:
- short circuit: typical < 360 Ω, certain < 100 Ω
- open circuit: typical < 0.35 mA, certain < 0.05 mA
switching points 24 V: ON > 8 V, OFF < 3 V
switching points 5 V: ON > 2.7 V, OFF < 2.3 V
Voltage8.2 V , typical
Indicators/settings
LED indicatorLED green: supply
LED red: line fault
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1
Conformity
Electromagnetic compatibilityNE 21
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100
Vibration resistancefrequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ± 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz
Damaging gasmodule G3
Mechanical specifications
Protection degreeIP20 (module) , a separate housing is required acc. to the system description
Connectionwire ends or shielded cable tail
wiring connection: separately covered Ex e terminals required
Massapprox. 750 g
Dimensions57 x 107 x 132 mm (2.2 x 4.2 x 5.2 in)
Data for application in connection with Ex-areas
EC-Type Examination CertificatePTB 97 ATEX 1074 U , PTB 97 ATEX 1075 (system) , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II 2 G Ex d IIC
Electrical isolation
Input/power supply, internal bussafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/ECEN 60079-0 , EN 60079-1
International approvals
IECEx approvalpending


Назад в раздел