Digital Output with Position Feedback | LB2002C

Артикул: LB2002C
Наименование: Digital Output with Position Feedback | LB2002C
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • 1 digital output, 2 digital inputs
  • Output voltage 24 V, max. internal resistance 210 Ω
  • Installation in Zone 2, Zone 22, or safe area
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog
  • Module can be exchanged under voltage (hot swap)

Datasheet as PDF in following languages:


Technical Data: LB2002C

Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies LB9***
Power consumption1.8 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer specific bus to standard com unit/bus coupler
Input
Number of channels2
Suitable sensorsmechanical contacts, NAMUR proximity switches, 2-wire initiators
Connectionterminals 2+, 5-; 3+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Switching point/switching hysteresis1.2 ... 2.1 mA / ± 0.2 mA
Voltage8.2 V , typical
Output
Number of channels1
Suitable field devicessolenoid valves, acoustic alarms and LED indicators (without line fault detection)
Connectionterminals 1+, 4-
Watchdogoutput off 0.5 s after serious fault
Indicators/settings
LED indicatorLED green: supply
LED yellow: signal (status), per channel
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1
Conformity
Electromagnetic compatibilityNE 21
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F) , 70 В°C (non-Ex)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100
Vibration resistancefrequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ± 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz
Damaging gasfor plugs: 21 days in 25 ppm SO2, at 25 В°C and 75 % rel. humidity, device G3
Mechanical specifications
Protection degreeIP20 (module) , mounted on backplane
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Massapprox. 110 g
Dimensions16 x 100 x 103 mm (0.63 x 3.9 x 4 in)
Data for application in connection with Ex-areas
Declaration of conformityPF 08 CERT 1234 X
Group, category, type of protection, temperature classEx-Hexagon II 3G Ex nA [ic] IIB T4
Electrical isolation
Input/power supply, internal bussafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/power supply, internal bussafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/ECEN 60079-0 , EN 60079-11 , EN 60079-15
International approvals
IECEx approvalBVS 09.0037X


Назад в раздел