Transformer Isolated Barrier for the Connection of Passive Contacts | KSD2-BI-4

Артикул: KSD2-BI-4
Наименование: Transformer Isolated Barrier for the Connection of Passive Contacts | KSD2-BI-4
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • 4-channel
  • 24 V DC supply voltage
  • Power Rail bus
  • EMC acc. to NAMUR NE 21

Datasheet as PDF in following languages:


Technical Data: KSD2-BI-4

Supply
ConnectionPower Rail
Rated voltage20 ... 30 V DC
Ripple< 10 %
Power consumption1.2 W
Input
Connectionterminals 1-, 2+, 3-; 4-, 5+, 6-
Open loop voltage24 V
Short-circuit currentapprox. 2 mA
Output
InterfaceCAN protocol via Power Rail bus
ConnectionPower Rail
Transfer characteristics
Switching frequency≤ 10 Hz
Electrical isolation
Input/power supply, internal busbasic insulation acc. to EN 50178, rated insulation voltage 300 Veff
Directive conformity
Electromagnetic compatibility
Directive 89/336/EECEN 61326
Explosion protection
Directive 94/9/ECEN 50021
Standard conformity
Insulation coordinationEN 50178
Electrical isolationEN 50178
Electromagnetic compatibilityNE 21
Protection degreeIEC 60529
Climatic conditionsIEC 60721
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Damaging gasacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Protection degreeIP20
Connectionterminal connection ≤ 2.5 mm2
Massapprox. 100 g
Dimensions20 x 100 x 115 mm (0.8 x 3.9 x 4.5 in)
MountingDIN rail mounting
Data for application in connection with Ex-areas
Statement of conformityTГњV 00 ATEX 1617 X , observe statement of conformity
Group, category, type of protection, temperature classEx-Hexagon II 3G EEx nA II T4


Назад в раздел