HART Transmitter Power Supply | KSD2-CI-S-Ex2.H

Артикул: KSD2-CI-S-Ex2.H
Наименование: HART Transmitter Power Supply | KSD2-CI-S-Ex2.H
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • 2-channel
  • Input EEx ia IIC
  • 24 V DC supply voltage
  • 4 limit values per channel
  • Device installation in Zone 2
  • Lead breakage (LB) and short-circuit (SC) monitoring
  • Transfer of HART signals
  • Power Rail bus
  • EMC acc. to NAMUR NE 21

Datasheet as PDF in following languages:


Technical Data: KSD2-CI-S-Ex2.H

Supply
ConnectionPower Rail
Rated voltage20 ... 30 V DC
Ripple< 10 %
Power loss1.8 W
Power consumption2.5 W
Input
Connectionterminals 1, 2, 3; 4, 5, 6
Input signal0 ... 20 mA or 4 ... 20 mA
Input resistanceapprox. 325 Ω , terminals 1, 2 or 4, 5
Transmitter supply voltage> 16.5 V at 20 mA
Line fault detectionbreakage I ≤ 0.8 mA , short-circuit I > 23.2 mA
Output
InterfaceCAN protocol via Power Rail bus
ConnectionPower Rail
Transfer characteristics
Deviation0.1 % of the input signal range at 20 В°C (68 В°F)
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Conformity
Insulation coordinationEN 50178:1997
Electromagnetic compatibilityNE 21:2006
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Mechanical specifications
Protection degreeIP20
Connectionterminal connection ≤ 2.5 mm2
Massapprox. 150 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in)
MountingDIN rail mounting
Data for application in connection with Ex-areas
EC-Type Examination CertificateBVS 04 ATEX E 086 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1)G [Ex ia] IIC
Ex-Hexagon II (1) D [Ex iaD]
SupplyPower Rail
Maximum safe voltage40 V DC (Attention! Um is no rated voltage.)
SignalCAN bus and HART (Power Rail)
Maximum safe voltage60 V DC (Attention! Um is no rated voltage.)
HART-connectionterminals 10-, 11+, 12+
Maximum safe voltage60 V DC (Attention! Um is no rated voltage.)
Inputterminals 1-, 2+; 4-, 5+
Voltage27 V
Currentnegligibly small
Voltage28 V
Current115 mA
Outputterminals 2-, 3+; 5-, 6+
Voltage26 V
Current93 mA
Power540 mW (linear characteristic)
Statement of conformityPepperl+Fuchs
Group, category, type of protection, temperature classEx-Hexagon II 3G Ex nA IIC T4 X
Electrical isolation
Input/power supply, internal bussafe electrical isolation acc. to IEC 60079-11:2007, voltage peak value 375 V
Directive conformity
Directive 94/9/ECEN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007 , EN 60079-15:2005


Назад в раздел